โ˜€๏ธ Off-Grid Power: Solar, Batteries & Creek Hydro

Making and storing electricity with no grid: what you really need, sizing solar for our dark winters, salvaging panels, controllers and inverters, keeping lead-acid and lithium batteries alive and safe, wiring, charging from a generator or car, and creek hydro, which is strongest when solar is weakest. The books are in Off-Grid-Power\ (Solar-PV, Batteries, Electrical-Basics, Micro-Hydro), with homemade generators in Engines-Motors\Motors-as-Generators, solar well pumps in Water-Wells-Pumps\Pumps-No-Grid, and Practical Action's battery and lighting briefs in Homestead-Skills\Household-Make-Do. The short version is in Illinois Valley โ€” Start Here.

โš ๏ธ Rules that prevent the worst outcomes


๐Ÿ“‹ Start with a load list

For each thing you'll run, multiply watts ร— hours a day = watt-hours (Wh) a day, and add them up (Sandia, p. 16). Take watts from the nameplate or a plug-in watt meter. An example (use your own numbers):

Item Watts Hours a day Wh a day
4 LED bulbs 40 5 200
Laptop 50 4 200
Radio and phone charging 20 5 100
Fridge or freezer (watt-meter reading) โ€” โ€” 450
Inverter idling 10 5 50
Total 1,000 Wh = 1 kWh

Pick the system voltage (Arizona, p. 5):

Daily load Battery voltage
Under 1 kWh 12 V
1โ€“4 kWh 24 V
Over 4 kWh 48 V

Keep steady current under 100 A (NRCS, p. 31).

๐Ÿ“š Go deeper: Sandia Sizing Small Off-Grid Solar Systems โ€” the load worksheet; Arizona Extension Stand-Alone PV Components โ€” every part, in plain words. Pictures: how the parts connect, Arizona p. 1, PA Solar PV p. 4, Photovoltaic system.

โ˜€๏ธ Our sun, month by month

Average "peak sun hours" a day at Medford, the nearest station, for a panel facing south tilted at our latitude, 42ยฐ (NREL Redbook, p. 181):

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Year
2.3 3.5 4.6 5.6 6.2 6.5 7.1 6.9 6.4 4.8 2.4 1.9 4.9

A solar panel seen from the side, tilted about 57 degrees for winter, 42 degrees year-round and never flatter than 10 degrees, facing the low December sun in the south Tilt steeply for our dark Decembers: about 57ยฐ in winter, 42ยฐ year-round, never below 10ยฐ (a diagram drawn for this guide).

๐Ÿ“š Go deeper: NREL Solar Radiation Data Manual โ€” Medford, every tilt, every month; Practical Action Solar PV โ€” tilt and sizing basics. Pictures: setting up a panel, PA Solar PV p. 1, Solar panel.

๐Ÿงฎ A worked example

Panels: panel kW = (kWh a day รท sun hours) ร— 1.2 for losses (Sandia, p. 20). For the 1 kWh load above:

Check: each rated panel watt gives about 0.85 Wh per sun hour (Practical Action, p. 4), and 630 ร— 0.85 ร— 1.9 โ‰ˆ 1,020 Wh.

Batteries: only 40% of a lead-acid label is usable (IEA, p. 17), so label Wh needed = daily Wh ร— days of backup รท 0.4. Above 40ยฐ latitude the IEA suggests 7โ€“9 days of backup for solar alone (same page): 17,500โ€“22,500 Wh of label for 1 kWh a day. Four 6 V, 220 Ah golf-cart batteries in series (drawing) make 24 V ร— 220 Ah = 5,280 Wh, about 2 days at 40% (arithmetic).

The cheaper fix: use less in winter, add panels (salvaged ones are plentiful), and fill the gap with creek hydro or a generator. When either more panels or more batteries would do, add panels; don't put a new battery into an aged bank (IEA, p. 38).

Controller: at 24 V with an MPPT controller, 630 W รท 24 V ร— 1.25 โ‰ˆ 33 A, so a 40 A controller (Arizona, p. 4).

๐Ÿ“š Go deeper: Sandia, p. 20 โ€” a full worked example; IEA Lead-Acid Battery Guide, p. 17 โ€” battery sizing. Pictures: 2 V cells wired into a 24 V bank, Arizona p. 5.

๐Ÿ” Salvaging and testing panels

Count the cells: 36 cells is a "12 V" panel; 60 cells give about 30 V, and 72 cells about 36 V (Arizona, p. 2; reading a panel's label). House-roof panels are 60- or 72-cell; they charge a 12 or 24 V bank well only through an MPPT controller (rule of thumb).

Rooftop grid-tie systems go dead when the grid does. A grid-tied inverter "cannot operate disconnected from the grid" (Navy NWC TP 6563, p. 23; grid-tied system); modern string and micro-inverters shut down the same way, by design (rule of thumb). The panels are fine: rewire them through a charge controller to batteries.

Testing a used panel (Navy, pp. 26, 50โ€“51):

  1. Look for cracked glass and peeling layers (delamination).
  2. In clear sun, face the panel squarely at the sun.
  3. Open-circuit voltage (nothing connected): within 10% of the label, allowing for heat (hot panels read lower) (drawing).
  4. Short-circuit current (drawing): meter on its 10 A range across the leads, one panel at a time (rule of thumb): within 20% of the label.

Testing a used solar panel: first a meter on DC volts across the leads with nothing else connected, then the meter on its 10 amp range with the red lead in the 10 A jack Open-circuit volts first, then short-circuit amps on the 10 A range, one panel at a time (a diagram drawn for this guide).

A 20-year-old panel usually still makes 80โ€“90% of its label (rule of thumb). Wash panels with plain water early in the morning, so cold water can't crack hot glass (p. 26). Bypass diodes let current flow around a dead module; a blocking diode stops the battery draining back through the panels at night (p. 19).

๐Ÿ“š Go deeper: Navy Maintenance of Photovoltaic Power Systems โ€” testing and troubleshooting with only a voltmeter. Pictures: a stand-alone system, Navy p. 11, Solar cell.

๐ŸŽ›๏ธ Charge controllers and inverters

PWM MPPT
Panels Must match the battery (36-cell for 12 V) Any higher-voltage string, including 60/72-cell house panels
Wire Heavier Thinner, at higher voltage
Size it at Panel short-circuit amps ร— parallel strings ร— 1.25 Array watts รท battery volts ร— 1.25

(Arizona, pp. 3โ€“4; PWM controllers; MPPT controllers.) The IEA uses ร— 1.3, because sun off cloud edges can reach 1,300 W/mยฒ (IEA, p. 41).

A good controller has (IEA, p. 21):

Inverters: use pure sine-wave for electronics and radios (Arizona, p. 7), and size for the motor-start surge. Keep a spare controller and inverter in a Faraday can (EMP guide).

๐Ÿ“š Go deeper: IEA Recommended Practices for Charge Controllers โ€” set points and features; Arizona, p. 7 โ€” inverter types. Pictures: how controllers switch the charge, IEA p. 15, AC and DC loads with an inverter, Arizona p. 6.

๐Ÿ”‹ Choosing batteries and reading their charge

Batteries wear out. For storing energy without them (a high water tank, hot water, stone and ice), see Storing Energy Without Batteries.

Best to worst for solar: solar batteries; then leisure, golf-cart and traction batteries; then truck starting batteries. Avoid car batteries (IEA, p. 13). A car battery survives about 20 deep discharges. A deep-cycle battery emptied 80% each time lasts about 800 cycles; emptied 20%, about 6,000 (Practical Action Batteries, p. 5).

Count on 40% of the label: a battery is worn out at 80% of new capacity, and should give at most half of that a day: 0.8 ร— 0.5 = 0.4 (IEA, p. 17). Series adds volts; parallel adds amp-hours (drawing). No more than 3โ€“4 strings in parallel, all the same age and size, with equal cables (p. 18).

Four 6-volt, 220 amp-hour batteries in series make 24 volts and 220 amp-hours; two 12-volt, 100 amp-hour batteries in parallel make 12 volts and 200 amp-hours; one fuse at the bank's positive post Series adds volts, parallel adds amp-hours; the main fuse goes right at the bank's + post (a diagram drawn for this guide).

How full is it?

Three battery hydrometers: the scale is read where the acid's surface meets the float, 1.150 in a weak cell and 1.270 in a nearly full one Draw acid in with the bulb and read the float at the acid's surface: 1.150 is run down, 1.270 nearly full (NEETS 1, p. 95).

Heat and cold: at 14 ยฐF a battery gives only 60% of its capacity, and every 18 ยฐF above 68 ยฐF doubles plate corrosion (IEA, pp. 18โ€“19). A discharged battery can freeze and crack; protect it below about 19 ยฐF (IEA controllers, p. 31). Here: shade batteries from 100 ยฐF summer heat and insulate them for January cold snaps (the record low is โˆ’6 ยฐF) (rule of thumb).

Storage: recharge stored lead-acid batteries every 3โ€“6 months (IEA, p. 23), sealed ones every 3 (Practical Action, p. 6).

๐Ÿ“š Go deeper: IEA Lead-Acid Battery Guide for Stand-Alone PV โ€” choosing, sizing and care; Practical Action Batteries โ€” plain-language basics. Pictures: inside a lead-acid battery, Navy p. 20, parts of a cell, DOE-HDBK-1084 p. 17.

๐Ÿ’ง Keeping lead-acid alive

Watering: use distilled water, added after charging, up to the fill line. In freezing weather add water only if a charge follows, or it may freeze before it mixes (DOE-HDBK-1084, p. 44). If the plates show, top up at once; clean rainwater will do now and then (IEA, p. 25). Adding acid doesn't recharge a battery (NEETS 1, p. 97).

Equalizing is a deliberate overcharge that brings every cell up and stirs the acid (IEA, p. 27; gassing vs. voltage chart):

"Desulfators": plate sulfate from sitting deeply discharged "can never be recovered" (IEA, p. 23); equalizing restores cells that were only undercharged (p. 20). Treat pulse gadgets as unproven: equalize, then time the battery under a known load before trusting it (rule of thumb).

Cleaning: neutralize spilled acid with about 1 kg baking soda in 4 L water (2 lb per gallon), then rinse (DOE-HDBK-1084, pp. 44โ€“45). Grease the terminals (IEA, p. 25).

๐Ÿ“š Go deeper: DOE Primer on Lead-Acid Storage Batteries โ€” watering, charging and care; IEA controllers, p. 46 โ€” charge set points. Pictures: voltage and specific gravity through a charge, DOE-HDBK-1084 p. 29.

๐Ÿ’ฅ Battery safety

Hydrogen (DOE-HDBK-1084, pp. 22, 46):

Shorts: put the main fuse right at the battery's + terminal (fuse and disconnect), and connect the battery last, after all wiring is checked (IEA, p. 28). Take off rings and watches, and tape wrench handles (rule of thumb).

Acid and gases: goggles and rubber gloves; flush for 15 minutes. Overcharged batteries can also give off toxic arsine and stibine; the venting that keeps hydrogen low keeps them low too (DOE-HDBK-1084, p. 46).

Where batteries go: out of living areas and not under electrical panels. A lockable polyethylene tool box holds four L-16 batteries (Sandia, p. 52). Up to about 20 six-volt batteries in a large, drafty room may not need forced venting (p. 51).

๐Ÿ“š Go deeper: DOE-HDBK-1084 โ€” hydrogen, acid and toxic gases; Sandia, p. 51 โ€” battery rooms and boxes. Pictures: a stationary battery bank, DOE-HDBK-1084 p. 36, Goggles.

๐Ÿ”ฅ Lithium, LiFePO4 and salvaged packs

Types (Lighting Global, pp. 3, 10; cylindrical, prismatic and pouch cells):

Charging rules (Lighting Global, pp. 6โ€“8):

Salvaged e-bike and tool packs: stop using one that smells, changes color, heats, swells, leaks or makes odd noises. Charge it with its own charger, never on a bed or couch, and not after it's full (NFPA, p. 1). Discard swollen, dented or long-dead packs; never build packs from mixed salvaged cells without a balancing BMS; in fire season, charge in a detached shed, on stone (rule of thumb).

If one burns (FAA SAFO 09013): one cell's thermal runaway sets off the next, and the fire flares again and again.

  1. Put out the flames with water or any extinguisher.
  2. Soak the pack with water to cool it. Don't cover it, use ice, or pick it up.
  3. Get out of a room with a burning battery bank: the gas is toxic and flammable, and a pack can reignite hours or days later (fire FAQ, pp. 2โ€“3).

๐Ÿ“š Go deeper: Lighting Global Lithium-ion Batteries โ€” types, charging and storage; Home Lithium-Ion Battery Fire Safety FAQ โ€” fire behavior. Pictures: lithium batteries for solar, Arizona p. 5, Lithium-ion battery.

๐Ÿ”Œ Wiring, fuses and grounding

Voltage drop: volts lost = 2 ร— one-way feet ร— amps ร— (ohms per 1,000 ft) รท 1,000. Aim for 3โ€“5% loss between array and battery (IEA, p. 53). Longest one-way run for a 3% drop at 10 amps (copper; halve it for 20 A, double it for 5 A), from NEETS 4, p. 20 (arithmetic):

Wire Ohms per 1,000 ft 12 V 24 V 48 V
10 AWG 1.02 18 ft 35 ft 71 ft
8 AWG 0.641 28 ft 56 ft 112 ft
6 AWG 0.403 45 ft 89 ft 179 ft
4 AWG 0.253 71 ft 142 ft 285 ft
2 AWG 0.159 113 ft 226 ft 453 ft

Fuses must be DC-rated. Car blade and glass fuses are made for 32 V or less and can't safely stop the huge current of a battery short; keep them off battery and array circuits (Sandia, p. 42). Protect the battery cable with a current-limiting DC fuse (class T or RK5) close to the battery (p. 45). Use time-delay fuses where motors start (NEETS 3, p. 94).

Wiring of a small solar system: panels through a DC fuse to the charge controller, the controller's load terminals through a 10 amp fuse to 12-volt lights, and the battery bank with a fuse right at the positive post for each wire, a main class T or RK5 fuse to the inverter, and the DC negative bonded to a ground rod at one point Every wire leaving the battery's + post gets its own DC-rated fuse right at the post; connect the battery last (a diagram drawn for this guide).

Grounding: bond the DC negative to ground at one point only (Sandia, p. 31; example grounding system). Drive ground rods 8 ft deep with #6 copper (FM 5-424, p. 49), about 6 ft apart if you use several (p. 117). For lightning, use one ground electrode, bond all metal frames, and run + and โˆ’ wires side by side so they don't form loops (IEA Lightning, pp. 7, 13; bad and good module wiring).

A ground rod driven 8 feet down into moist soil, with number 6 copper wire wrapped and clamped at its top A ground rod driven 8 ft deep into moist soil, with #6 copper wire to it (FM 5-424, p. 49).

๐Ÿ“š Go deeper: Sandia PV Systems and the NEC โ€” fuses, disconnects, grounding; Army FM 5-424 โ€” ground rods. Pictures: crimpers and terminals, Sandia p. 21, wire on terminals, FM 5-424 p. 24, Crimp.

โ›ฝ Generators, cars and backfeed

Wrong: a generator plugged into a wall outlet sends power back through the house panel and out onto the power line, where it can kill a line worker. Right: a transfer switch connects the house panel to either the grid or the generator, never both A generator in a wall outlet sends power out onto the lines; a transfer switch connects the house to the grid or the generator, never both (a diagram drawn for this guide).

๐Ÿ“š Go deeper: CPSC Portable Generator Hazards โ€” CO and backfeed; Alternator and Regulator Servicing โ€” charging and testing. Pictures: how an alternator works, p. 8, Engine-generator.

๐ŸŒŠ Creek hydro, and why not wind

While Oregon's water laws are enforced, most Illinois Valley creeks are closed to hydro by state rule (see Start Here).

Measure the drop (head) (what head means): run a hose full of water downhill with a pressure gauge at the bottom; psi ร— 2.31 = feet of head (NCAT, p. 6).

Measure the flow: time how long the creek takes to fill a container: a 55-gal drum in 40 seconds is 82.5 gallons a minute (gpm) (NCAT, p. 3). For a bigger creek: width ร— average depth (sq ft) ร— float speed (ft per second) ร— 0.25 for a shallow rocky bed, up to 0.75 for a smooth one, gives cubic feet per second (cfs); 1 cfs = 449 gpm (p. 4; measuring a stream's cross-section).

Power from a creek โ‰ˆ gpm ร— feet of head รท 10 watts (NCAT, pp. 8โ€“9). A real case: 100 gpm with 35 ft of head left at the turbine (15 psi) gives about 200 W around the clock, nearly 5 kWh a day, to a 24 V bank (NRCan, p. 29). The rule predicts 350 W: small systems often fall short.

Measuring creek hydro: a hose full of water runs from the intake down the hill to a pressure gauge, and the drop is psi times 2.31 feet; flow is timed by how long the creek takes to fill a 55-gallon drum Head from a hose and a pressure gauge, flow from a drum and a watch (a diagram drawn for this guide).

Pipe size matters. Head lost per 100 ft of PVC (NCAT, p. 7):

Flow 2-in 3-in 4-in
25 gpm 1.3 ft 0.2 ft 0.04 ft
50 gpm 4.7 ft 0.7 ft 0.2 ft
100 gpm 16.8 ft 2.3 ft 0.6 ft
200 gpm 60.6 ft 8.4 ft 2.0 ft

Small wind is usually poor here. An off-grid wind system needs an average of at least 9 mph (DOE Small Wind, p. 20). Medford averages 4.7 mph, and 3.6 in December (Redbook, p. 181). Power rises with the cube of wind speed, so half the wind gives one-eighth the power (p. 11), and the rotor must sit 30 ft above anything within 300 ft (p. 7). Only exposed ridgetops are worth testing; put money into solar and hydro first (rule of thumb).

๐Ÿ“š Go deeper: NCAT Micro-Hydro Power โ€” measuring and sizing; NRCan Buyer's Guide โ€” battery systems; DOE Small Wind. Pictures: parts of a micro-hydro system, NRCan p. 6, high- and low-head layouts, NCAT p. 13, a battery-based hydro system, NRCan p. 28, Penstock, Weir.

โš ๏ธ Old advice in the library to ignore

๐Ÿ“š Go deeper: Lighting Global โ€” modern battery chemistries compared; Arizona Extension โ€” today's MPPT controllers and solar batteries, pictured; LED lamp.

๐Ÿ–ผ๏ธ Pictures & diagrams

Look before you try it. ๐Ÿ–ผ๏ธ = drawings in the books on this drive; ๐Ÿ“ท = photos in the offline Wikipedia.

How a system fits together

Panels, controllers and inverters

Batteries

Wiring, fuses and grounding

Creek hydro and wind


โ†‘ Contents